CP Examination & Lifting Road Contactor Panel (630A) – L. C. Switchgear

CP Examination & Lifting Road Contactor Panel (630A)

Product Number:
8800391

The Examination & Lifting Road Contactor Panel supplies the 630V DC Shore Supply to the examination road overhead conductor rails for the OST Overhead Switchable Trolleys.

The Examination & Lifting Road Contactor Panel consists of a 2 pole 630A 1000V DC Contactor with associated control equipment, earth monitoring equipment, 2 x 400A traction grade fuses, and a 4 pole 1250A 1000V DC Disconnector for maintenance. Local controls are fitted on the front of the Panel.

The Examination & Lifting Contactor Panel provides signals to the Overhead Status Indicators and to the Mimic Panel.

Applications:
Combined Assemblies & Frames (CA), Circuit Breaker (CB), Switchgear Enclosures (SE), Switch / Disconnector (SD),

Approvals:
LU approved,

Key Features

The 630V DC is then fed directly from the Contactor to the Road Shore Supply for the Overhead Switchable Trolleys (8800290) OR to the Lifting Shed Power Pedestals (8800291).

 

The 630V DC is fed to the 2 pole contactor via:

4 pole Isolating & Bonding Disconnector, which has interlocks for Maintenance and Secure Isolations. These prevent contactor operation and the 630V DC supply when maintenance is being performed.

The Contactor provides signals to the Overhead Status Indicators OSI and the Mimic Panel in the DDM Office.

When the Disconnector is moved to the Earthed position the outgoing supplies to the Examination or Lifting Sheds are earthed and can be locked, making them safe for maintenance.

Product Specifications:


On / Off load On Load
System Voltage 360V
Rated Voltage 1000V
Normal Current 630A
Length 1300mm
Depth 600mm
Height 2050mm
Weight 450kg

Construction

Core specs

Enclosure Type: Steel

IP Rating: IP55

The cubicle is a custom designed and built sheet metal assembly, painted to meet the customer specification. The cubicle has four sections, each with its own door, and one section with two doors

The individual doors and barriers provide segregation between the sections and the 630V DC sections also have polycarbonate screens behind the doors.