TFS Track Feeder Switch – Network Rail PA05/06563

The Track Feeder Switch (TFS) is required to bring isolations of the 750V DC conductor rail into line with the requirements of the Electricity at Work Regulations 1989. The TFS isolates the live conductor from its sources of energisation (Electricity at Work Act Regulation 12) and securely protects against inadvertent re-energisation from any source (Electricity at Work Act Regulation 13) by being connected to the negative pole of the supply via the bonding switch. The TFS can also isolate traction... see full details

NSCD Negative Short Circuiting Device

The Negative Short Circuit Device 2kA (NSCD) provides a short-circuit path between the DC Traction Supply and the Negative Return to protect against the inadvertent re-energisation of the circuit. The NSCD can be operated remotely via a SCADA Interface, locally via a Local Control Panel and at the NSCD itself for maintenance. The NSCD consists of a motorised 3.2kA Disconnector to provide the short-circuit path, a manual 2.5kA Disconnector to isolate the motorised Disconnector for maintenance, panel lighting and anti-condensation... see full details

CP Examination & Lifting Road Contactor Panel (630A)

The Examination & Lifting Road Contactor Panel supplies the 630V DC Shore Supply to the examination road overhead conductor rails for the OST Overhead Switchable Trolleys. The Examination & Lifting Road Contactor Panel consists of a 2 pole 630A 1000V DC Contactor with associated control equipment, earth monitoring equipment, 2 x 400A traction grade fuses, and a 4 pole 1250A 1000V DC Disconnector for maintenance. Local controls are fitted on the front of the Panel. The Examination & Lifting Contactor... see full details

DRC – 2kA 1P Depot Contactor Panel with Motor Driven Bonding Device

Single pole changeover switching of high power circuits, where a high short circuit withstand and high voltage isolation is required. The motor driven switch is to be used to bond the 750 Volt positive track feed connection to the negative rail and is electrically interlocked with its associated Contactor from which it obtains its control supply. Opening of the Contactor will cause the bonding device to close. The device is operated from the Contactor control circuit or automatically following the... see full details

COLR 725 Type Current On line Relay

The 725 Type Current On-Line Relay consists of a Bar and Shaft Type Contactor mounted in a stainless steel enclosure. This automatically switches on the tunnel lighting when the traction power supply is switched off or is lost due to a fault. see full details

Gap Jumper Lead

The Gap Jumper Lead is used to connect a supply to a stranded (Gapped) Train. This is where a train current collector shoe (pick up shoe) is no longer in connection with the power supply conductor rails. see full details

DC Disconnector – Otter OD1L – OD7R

The latest range of Otter switches and disconnectors is designed for high current DC applications including but not limited to; rail, trams, renewable energy, electric vehicle charging, DC distribution networks and industrial processes e.g. aluminium smelting, arc furnaces. The modular design adapts to various functions including isolation, fault making and load breaking. Designed and manufactured to high quality standards and comprehensively tested, ensuring high reliability and minimal maintenance. The switch can be offered as a standalone product, with or without... see full details

DC Switch – Otter OS1L – OS7L

The latest range of Otter switches and disconnectors is designed for high current DC applications including but not limited to; rail, trams, renewable energy, electric vehicle charging, DC distribution networks and industrial processes e.g. aluminium smelting, arc furnaces. The modular design adapts to various functions including isolation, fault making and load breaking. Designed and manufactured to high quality standards and comprehensively tested, ensuring high reliability and minimal maintenance. The switch can be offered as a standalone product, with or without... see full details

TDC2 Trackside Connection Box Double Link

A Substation Section Isolating links are used to connect and disconnect the power to the overhead lines. Once Isolated the Trackside Connection Box Links can be removed ensuring a safe working environment for the overhead lines. see full details

GJL Conductor Rail Gap Jumper Shoes (Pair)

The Gap Jumper Lead is used to connect a supply to a stranded (Gapped) Train. This is where a train current collector shoe (pick up shoe) is no longer in connection with the power supply conductor rails. The LCS Gap Jumper Lead design incorporates the following features: A shoe assembly that houses the conduction plate with integral magnets to suit various conductor rails, the cable connection point, cable restraint gland and conductor rail location guides. The conduction plate is made... see full details

PP 2 Pole Power Pedestal 200A

The Road 630V DC is then fed directly from the Contactor to the Power Pedestal. Two 110V AC control supply is also derived from the respective Contactor panel. The Shore Supply Plug is fitted with a Plug Engaged sensor which inhibits the application of Traction Power to the train unless a magnet in the train receptacle to detected. The Pedestal supplies Traction Power to trains in depot lifting sheds via a Shore Supply Plug. The Shore Supply Plug is stowed... see full details

PP 2 Pole Power Pedestal 150A

The Road 630V DC is then fed directly from the Contactor to the Power Pedestal. Two 110V AC control supply is also derived from the respective Contactor panel. The Shore Supply Plug is fitted with a Plug Engaged sensor which inhibits the application of Traction Power to the train unless a magnet in the train receptacle to detected. The Pedestal supplies Traction Power to trains in depot lifting sheds via a Shore Supply Plug. The Shore Supply Plug is stowed... see full details

OST 2 Pole Overhead Switchable Trolley (200A)

The Overhead Switchable Trolley mounts on a 4 inch wide overhead ‘I’ beam. The Road 630V DC is then fed directly from the Contactor to the 630V DC Traction Power supply overhead supply bars. The Trolley Brush collectors pick up the supply from the supply bars. Two 110V AC control supply collectors pick up the supply from two control bars fitted along the length of each road. The Shore Supply Plug is fitted with a Plug Engaged sensor which inhibits... see full details

OST 2 Pole Overhead Switchable Trolley (150A)

The Overhead Switchable Trolley mounts on a 4 inch wide overhead ‘I’ beam. The Road 630V DC is then fed directly from the Contactor to the 630V DC Traction Power supply overhead supply bars. The Trolley Brush collectors pick up the supply from the supply bars. Two 110V AC control supply collectors pick up the supply from two control bars fitted along the length of each road. The Shore Supply Plug is fitted with a Plug Engaged sensor which inhibits... see full details

COSI Cleaning Road Overhead Status Indicator

The Cleaning Road Overhead Status Indicator is a roof mounted unit that displays the electrical status of the roads fitted with ground mounted conductor rails. It is controlled by the associated Cleaning Road Contactor. The control circuit is easily accessible at the end of the unit. The unit is controlled by a high integrity circuit that is built into the Cleaning Road Contactor Panel. An Audible Alarm and Flashing Beacon are activated as a warning prior to traction current being... see full details

TI Trackside Indicators

Trackside Indication for conductor rail: Power On Power Off Indication is by low maintenance LED’s and can be mono-colour or dual-colour. Used on the Dockland Light Railway System see full details

LVAC Tunnel Lighting Switchboard (50A)

Single phase AC Switchboard with an automatic changeover from the LU supply to a DNO supply when the LU supply is lost. The switchboard feeds four tunnel lighting circuits which are automatically invoked when their associated traction supply is switched off. The switchboard can be divided into three sections to enable installation into limited access switch rooms. see full details

LVAC Two Panel Modular Switchboard

The system comprises two incoming 400V-440V 100A AC supply circuits. Each consists of an incoming 4 pole 690V 100A Switch-Disconnector followed by a 3 pole 660V 100A contactor and then an isolating 4 pole 690V 100A Switch-Disconnector. The outputs from the isolating Switch-Disconnectors feed a bus and this is sectioned with a 4 pole 690V 100A bus isolating Switch-Disconnector. To customer specification NR/SP/ELP/21026 The bus feeds the four outgoing supply circuits via 4 pole 1000V 63A Switch-Fuses. see full details

IBD Isolator & Bonding Device

Designed to provide depot road isolation and interlocked negative bonding of conductor rails at Various Main Line Depots. The manual handles are interlocked so that the Isolator cannot be closed at the same time as the Bonding Switch. see full details

MLU SBI Shed Board Isolator

2kA 2 Pole DC Manual Shed Board Isolator 8800287-V01 The Shed Board Isolator supplies the 630V DC Shore Supply to a suite of Contactor Panels and contains an interlocked, manual, 2 pole 630A 1500V DC, off-load Disconnector. see full details

CRCP Cleaning Road Contactor Panel (630A)

The Cleaning Road Contactor Panel supplies the 630V DC Shore Supply to the cleaning road conductor rails. The Cleaning Road Contactor Panel consists of a 2 pole 630A 1000V DC Contactor with associated control equipment, earth monitoring equipment, 400A traction grade fuses, and a 4 pole 1250A 1000V DC Disconnector for maintenance. Local controls are fitted on the front of the Panel and it can also be operated via a Remote Control panel. The Cleaning Road Contactor Panel provides signals... see full details